OVERVIEW

About 3-Phase & 1-Phase Online / Offline UPS

A UPS keeps critical loads running through mains outages and shields them from voltage and frequency disturbances. IEC 62040-3 groups UPS by how much the output depends on the mains: VFD (offline or standby), VI (line-interactive, where voltage is regulated but frequency follows the mains) and VFI (online double conversion, where output is independent of mains voltage and frequency). Double-conversion units rectify the input to DC, keep the battery charged and rebuild a clean AC output through an inverter, so there is no transfer break.

Microtech supplies single- and three-phase UPS from Delta, APC, Neumeric and Sarthak. As examples of what is available, Delta's Amplon family covers single-phase UPS from 1 kVA, and its Ultron HPH three-phase series is fully rated (kVA equals kW) with 96% AC-AC efficiency, 99% in ECO mode and input current distortion below 3%. APC's Easy UPS 3S offers three-phase 400 V double-conversion online units from 10 to 40 kVA.

We size the UPS from your load's kW, power factor and required backup time, and supply the matched battery bank and installation.

SPECIFICATIONS

Key specifications

3-Phase & 1-Phase Online / Offline UPS — key specifications
Phase1-phase and 3-phase input/output
TopologiesOnline double conversion (VFI) and line-interactive / offline (VI / VFD)
Single-phaseFrom 1 kVA (Delta Amplon family)
Three-phase10–40 kVA online (APC Easy UPS 3S); 20–120 kW (Delta Ultron HPH)
Efficiency (Delta Ultron HPH)96% AC-AC, 99% ECO mode; iTHD < 3%
BatteriesExternal battery bank sized to required backup time
Classification standardIEC 62040-3
FEATURES

Features & benefits

  • No-break supply for servers, PLCs and instrumentation with online UPS
  • Lower-cost line-interactive option for office IT loads
  • Fully rated three-phase units where kVA equals kW
  • High-efficiency ECO mode on selected online models
  • Battery bank sized to backup time and load
  • Installation, battery replacement and AMC support
APPLICATIONS

Where it’s used

  • Server rooms and data centres
  • PLC, SCADA and process control systems
  • Hospitals and diagnostic equipment
  • Banks, offices and call centres
  • Laboratories and instrumentation
  • Telecom and CCTV systems
STANDARDS

Standards & compliance

IEC 62040-3 – UPS performance and test requirements
COMMON QUESTIONS

3-Phase & 1-Phase Online / Offline UPS — FAQs

Online or offline UPS – which do I need?

An online (double-conversion) UPS rebuilds its output continuously, so the load never sees a mains disturbance or transfer break – the right choice for servers, PLCs and process instruments. A line-interactive or offline UPS costs less and suits office IT that can tolerate a brief transfer – close to 10 ms for a standby design.

What does VFI mean on a UPS datasheet?

VFI is the IEC 62040-3 class for UPS whose output is independent of mains voltage and frequency – in practice, online double-conversion units. VI is line-interactive and VFD is standby or offline.

How do you size the UPS and battery?

We add up the load in kW and kVA, allow for power factor, inrush and growth, then size the battery for the backup time you need. A list of connected equipment is enough to start.