OVERVIEW

About Current Transformers

A current transformer (CT) steps a large feeder current down to a standard 5 A or 1 A secondary, so meters and relays can measure it safely. We supply low-tension CTs from Selec and Procom for switchboards, MCCs, APFC panels and DG panels.

Procom's LT range runs up to 6000/5 A in rectangular resin-cast form. It covers moulded rectangular and round CTs, resin-cast ring and rectangular types, wound-primary CTs for low currents, 5P10 protection CTs and core-balance CTs (CBCTs) for earth-leakage relays. Selec adds tape-wound, busbar-type and split-core CTs. Split-core types clamp around an existing conductor without disconnecting it, which makes retrofit metering simple.

The ratio is only half the selection. A metering CT needs the right accuracy class, and its VA burden must cover the meter plus the resistance of the secondary leads. A protection CT needs a protection class such as 5P10 so it stays accurate at fault current. We check all three against the meter, the relay and the lead length.

SPECIFICATIONS

Key specifications

Current Transformers — key specifications
CT typesMoulded (ring / rectangular), resin-cast ring and rectangular, wound-primary, tape-wound, busbar, split-core, CBCT
Primary ratings5/5 A wound-primary up to 6000/5 A resin-cast (Procom); split-core 100–6000 A (Selec)
Secondary5 A standard; 1 A on request
Metering accuracyClass 0.5 and Class 1 (Procom); Class 0.5 to 5 across Selec types
Protection class5P10 resin-cast; 5P5 and PS class listed (Procom)
Rated burden2.5 VA to 20 VA, depending on ratio and type
CBCT1000-turn core-balance CTs, 37.5 mm to 200 mm window; larger resin-cast CBCTs (Procom)
Moulded housing (Procom PRO)Nylon UL 94-V2, IP20, finger-safe terminal cover
Selec busbar CT approvalsCE, UL, ASTA
FEATURES

Features & benefits

  • Window sizes and busbar slots to suit standard busbar sections
  • Split-core CTs for retrofit metering without a shutdown on the conductor
  • Wound-primary CTs give usable accuracy at low currents (down to 5 A)
  • Dual terminals for a CT shorting link on Procom moulded CTs
  • Protection-class CTs for overcurrent and earth-fault relays
  • CBCTs matched to earth-leakage relays
APPLICATIONS

Where it’s used

  • LT switchboards and PCC incomers
  • MCC feeders and motor protection
  • APFC panels
  • DG and AMF panels
  • Energy metering and sub-metering
  • Earth-leakage protection
STANDARDS

Standards & compliance

IS 16227 (Part 2) / IEC 61869-2 — instrument transformers: current transformers
COMMON QUESTIONS

Current Transformers — FAQs

How do I size a current transformer?

Start from the feeder's full-load current and pick the next standard ratio up. Then check the burden: the CT's rated VA must cover the connected meter or relay plus the resistance of the wire run to it.

What is the difference between a metering CT and a protection CT?

A metering CT, such as Class 0.5 or 1, is accurate around normal load current. A protection CT, such as 5P10, stays within its error limit up to many times rated current, so a relay can see a fault correctly. Use the class that matches the device connected to the CT.

What is a CBCT used for?

A core-balance CT surrounds all the phase conductors, plus neutral where present, of a feeder. It measures the residual current that leaks to earth and feeds an earth-leakage or earth-fault relay.

Can I fit a CT without disconnecting the cable?

Yes, with a split-core CT. Selec's split-core range opens around the existing conductor and is offered from 100 A to 6000 A.

Gloved hands terminating wires inside an open industrial control panel